Real-time input and output power monitoring,Diagnostics and fault indication,Modular and hot swappable,Configurable alarms,R/S 485 HART communication,Asset management integration - EDDL/DTM,ATEX, IECEx, and cULus approvals for Div 2/Zone 2

Type : diagnostic bus: RS 485
Rated voltage : 90...250 V AC, 44 ... 66 Hz; 90 ... 300 V DC
Rated current : 100 mA max
Fault signal : Form C Relay
50 V DC @ 0.6 A
30 V DC @ 2 A
Input/Output : 4.25 kV DC
Field circuit/control circuit : Primay to Diagnostic Module Isolation: 4.25 kVDC
External RS485 to primary isolation: 4.25 kVDC
Internal RS485 to primary isolation: 4.25 kVDC
Secondary to Diagnostic Module: 2.12 kVDC
External RS485 to secondary isolation: 2.12 kVDC
Internal RS485 to secondary isolation: 2.12 kVDC
Display elements : LCD Status Screen
Diagnostic Module LED
Primary (AC Input) Monitors LED
Secondary (DC Output) Monitors LED
Power Supply Module LED
Electromagnetic compatibility : Refer to DoC for all directives and standards met.
Electromagnetic compatibility : NE 21:2006
Degree of protection : IEC 60529
Shock resistance : EN 60068-2-27
Vibration resistance : EN 60068-2-6
Ambient temperature : -20 ... 60 °C (-4 ... 140 °F)
Storage temperature : -40 ... 85 °C (-40 ... 185 °F)
Relative humidity : < 95 % , non-condensing
Shock resistance : 15 g , 11 ms
Vibration resistance : 1 g , 58 ... 150 Hz
Connection type : motherboard specific
Housing material : Powder Coated, 1010 Cold Rolled Steel
Degree of protection : IP20
Mass : approx. 1.16 kg (2.56 lbs)
Dimensions : 134 x 33 x 268 mm (5.3 x 1.3 x 10.6 inch)
Certificate : DEMKO 12 ATEX 1103387X
Directive conformity :
UL approval : cULus Listed
E230669
E350173
IECEx approval : IECEx UL 13.0082X
Ex ic ec nC IIC T4 Gc
Supplementary information : Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

  • 最小起订量 : 1