24 V DC to 28 V DC input,2 inputs with 1 output,Output 24 V DC, 20 A,Housing width 32 mm,Built-in decoupling mosfets for 1+1 and N+1 redundancy,Automatic load sharing,Reverse input polarity protection,Easy wiring: distribution terminal for negative pole included,Redundancy status indicator,Suitable for Zone 2/Div. 2 mounting
Voltage drop : input to output
0.1 ... 0.5 V at input 2 x 5 A
0.2 ... 0.5 V at input 2 x 10 A
0.24 ... 0.5 V at input 2 x 12 A
load share dependent Power dissipation : 1.7 W no load
2.6 ... 4.7 W at input 2 x 5 A
5.6 ... 8.7 W at input 2 x 10 A Rated voltage : 24 ... 28 V Voltage range : 18 ... 35 V DC Current : 2 x 12 A at ambient temperature < 45 °C (113 °F)
2 x 10 A at ambient temperature 70 °C (158 °F)
2x 17 mA for max. 5 s
for lower output currents see technical information Voltage : 24 ... 28 V DC Current : 24 A at ambient temperature < 45 °C (113 °F)
20 A at ambient temperature < 70 °C (158 °F)
32.5 A for max. 5 s
max. 26 A in overload or short circuit mode (voltage < 6 V DC) Connection : terminals 13, 14 : relay contact load share
terminals 23, 24 : relay contact redundancy Output type : relay contact load share
- contact is closed if the adjustment of the output voltages are sufficient
- contact is open if an even load share does not occur and readjustment of the output voltage is required
relay contact redundancy
- contact is closed if no fault is detected
- contact is open if one or both input voltages are below 22 V DC or above 30 V DC
- contact is open if the output current is higher than the adjusted value of the output current
- contact is open if an internal defect of the device is detected Contact loading : max. 60 V DC/0.3 A ; 30 V DC/1 A ; 30 V AC/0.5 A resistive load
min. 1 mA at 5 V DC Input/Output : SELV/PELV Display elements : LED green: output status
- LED lights up if the output current is smaller than the adjusted value of the output current
LEDs green: load share status
- LEDs indicate the load share status between the two power supplies
LED green: redundancy status
- LED lights up if no fault is detected
- LED flashes if one ore both input values are below 22 V or above 30 V
- LED flashes if the output current is higher than the adjusted value of the output current
- LED flashes if an internal defect is detected Control elements : rotary switch Configuration : setting of the output current via rotary switch
- switch setting to 5 A in combination with two 5A power supplies (1+1 redundancy)
- switch setting to 10 A in combination with two 10A power supplies (1+1 redundancy)
- switch setting to 20 A for N+1 redundant systems Electromagnetic compatibility : Low voltage : RoHS : Degree of protection : EN 60529 Shock resistance : EN 60068-2-27 Vibration resistance : EN 60068-2-6 Ambient temperature : -40 ... 70 °C (-40 ... 158 °F) , see technical information Storage temperature : -40 ... 85 °C (-40 ... 185 °F) Relative humidity : 5 ... 95 %, noncondensing Shock resistance : 20 g , 11 ms or 30 g , 6 ms Vibration resistance : 2 ... 17.8 Hz : ± 1.6 mm , 17.8 ... 500 Hz : 2 g Housing material : aluminum alloy , galvanized steel Degree of protection : IP20 Connection : Mass : approx. 310 g Dimensions : 32 x 124 x 117 mm (W x H x D) , without DIN mounting rail Mounting : on 35 mm DIN mounting rail acc. to EN 60715:2001 ATEX approval : Directive conformity : UL approval : E223176 IECEx approval : Supplementary information : Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.