380 V AC to 480 V AC wide-range inputs,Output 24 V DC, 40 A, 960 W, 3-phase,Housing width 110 mm,Efficiency up to 95.3 %,Minimal inrush current surge,Shutdown input,Remote control for ON/OFF,DC OK relay contact,Current sharing for parallel use

Efficiency : 95.3 % at 3 x 400 V AC
95.2 % at 3 x 480 V AC
Power dissipation : 47.3 W at 3 x 400 V AC
48.4 W at 3 x 480 V AC
Current : 1.65 A at 3 x 400 V AC
1.35 A at 3 x 480 V AC
for lower output currents see technical information
Inrush current : 4.5 A peak at 3 x 400 V AC, temperature-independent
4.5 A peak at 3 x 480 V AC , temperature-independent
Voltage : 3 x 380 ... 480 V AC (-15 %/+20 %), 50 ... 60 Hz (±6 %)

Capacity factor : 0.88 at 3 x 400 V AC
0.9 at 3 x 480 V AC
Remote control : terminals 15, 16
remote control for ON/OFF and shutdown input
Rated voltage : 24 V DC
Voltage range : 24 ... 28 V DC
factory setting: 24.1 V
Rated current : 40 A
Current : continuous:
40 ... 34.3 A
short-term up to 4 s:
60 ... 51.5 A
linear power derating see technical information
Power : 960 W
Ripple : max. 100 mV pp
Hold-up time : 25 ms at 3 x 400 V AC
25 ms at 3 x 480 V AC
Overload behavior : constant current mode
Short-circuit current : typ. 46 A continuous, load impedance < 10 mΩ
Voltage limitation : typ. 30.5 V DC
max. 32 V DC
Connection : terminals 13, 14
Output type : relay contact DC OK
- contact is closed if the output voltage is > 90 % of the adjusted output voltage
Contact loading : max. 60 V DC/0.3 A ; 30 V DC/1 A ; 30 V AC/0.5 A resistive load
min. 1 mA at 5 V DC
Input/Output : SELV/PELV
Display elements : LED green: status DC OK
- LED lights up if the output voltage is > 90 % of the adjusted output voltage
LED red: overload
- LED lights up if the output voltage is < 90 % of the adjusted output voltage or in case of short circuit
- flashes if the shutdown has been activated or if the device has shut down due to overtemperature
Control elements : potentiometer , plug-in jumper
Configuration : setting of the output voltage via potentiometer
setting of the operating mode
- plug-in jumper plugged in: parallel use operating mode
- plug-in jumper not plugged in: single use operating mode
setting of the shutdown input:
- plug-in jumper plugged in: device switches off
Electromagnetic compatibility :
Low voltage :
RoHS :
Degree of protection : EN 60529
Shock resistance : EN 60068-2-27
Vibration resistance : EN 60068-2-6
Ambient temperature : -25 ... 70 °C (-13 ... 158 °F) , see technical information
Storage temperature : -40 ... 85 °C (-40 ... 185 °F)
Relative humidity : 5 ... 95 %, noncondensing
Shock resistance : 15 g , 6 ms or 10 g , 11 ms
Vibration resistance : 2 ... 17.8 Hz : ± 1.6 mm , 17.8 ... 500 Hz : 1 g
Housing material : aluminum alloy , galvanized steel
Degree of protection : IP20
Connection :
Mass : approx. 1500 g
Dimensions : 110 x 124 x 127 mm (W x H x D) , without DIN mounting rail
Mounting : on 35 mm DIN mounting rail acc. to EN 60715:2001
UL approval : E223176
Supplementary information : Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.