2-, 3- and 4-wire technology, 4 mA ... 20 mA analog output,High accuracy in total ambient temperature range,Universally PC programmable for various signals,Fault signal on sensor break or short circuit, presettable to NAMUR NE43,Online configuration during measurement using SETUP connector,Customer specific linearization,EMC acc. to NAMUR NE 21
Connection : terminals 1, 2 Rated voltage : 8 ... 35 V DC
8 ... 30 V DC for hazardous area Sensor types : resistance thermometer (RTD):
- Pt100, Pt500, Pt1000 acc. to IEC 751 and Ni100, Ni500, Ni1000 acc. to DIN 43760
resistance transmitter (Ω)
thermocouple (TC):
- B (PtRh30-PtRh6), C (W5Re-W26Re), D (W3Re-W25Re), E (NiCr-CuNi), J (Fe-CuNi), K (NiCr-Ni),
L (Fe-CuNi), N (NiCrSi-NiSi), R (PtRh13-Pt), S (PtRh10-Pt), T (Cu-CuNi), U (Cu-CuNi), MoRe5-MoRe41 acc. to IEC 584, part 1
voltage transmitter (mV) Connection : resistance thermometer (RTD):
- 2-wire connection: terminals 3, 6
- 3-wire connection: terminals 3, 5, 6
- 4-wire connection: terminals 3, 4, 5, 6
resistance transmitter (Ω):
- 2-wire connection: terminals 3, 6
- 3-wire connection: terminals 3, 5, 6
- 4-wire connection: terminals 3, 4, 5, 6
thermocouple (TC): terminals 4, 6 Cold junction compensation : internal (Pt100) or external (0 ... 80 °C (273 ... 353 K)), accuracy ± 1 K Lead resistance : resistance thermometer (RTD): max. 11 Ω per line Current : resistance thermometer (RTD): sensor current ≤ 0.6 mA
thermocouple (TC): sensor current 30 mA Connection : terminals 1, 2 Current limit : ≤ 25 mA Load : (Vs - 8)/0.025 A Switch-on delay : 4 s , during power up Ia = 3.8 mA Output signal : 4 ... 20 mA, 20 ... 4 mA temperature linear, resistance linear, voltage linear Residual ripple : Upp ≤ 5 V at Ub ≥ 13 V, fmax = 1 kHz Response time : 1 s Self current consumption : max. 3.5 mA Signal on alarm : measuring range undercut: linear drop to 3.8 mA
exceeding measuring range: linear rise to 20.5 mA
sensor breakage, sensor short circuit: ≤ 3.6 mA oder ≥ 21.0 mA can be set up Input/Output : safe galvanic isolation acc. to EN 50020, 3.75 kV AC Reference operating conditions : calibration temperature 23 °C (296 K) ± 5 K Maximum measured error : resistance thermometer (RTD): 0.2 ... 0.5 K or 0.08 ... 0.2 %
resistance transmitter (Ω): ± 0.1 ... 1.5 Ω or 0.08 ... 0.12 %
thermocouple (TC): typ. 0.5 ... 2.0 K or 0.08 %
voltage transmitter: ± 20 µV or 0.08 % Ambient conditions : Degree of protection : IP00/IP66 installed Connection : Terminals for wires max. 1.75 mm 2, undetachable screws Material : housing: PC
potting: PUR Mass : approx. 40 g Dimensions : ∅44 x 22,5 mm (1.7 x 0.9 inch) Construction type : connection head acc. to DIN 43729 form B, field housing Configuration : via PC operating software, configuration set TXU 10L
interface: PC interface connection cable TTL-/-RS 232 with plug Explosion-hazardous area : ZELM 07 ATEX 0352 X , for additional certificates see www.pepperl-fuchs.com Type of protection : II 1G Ex ia IIC T6/T5/T4 Directive conformity : Conformity : Supplementary documentation : technical information TI070O
operating instructions KA141O
safety information SI085O (ZELM 07 ATEX 0352 X) Supplementary information : EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.