40 mm non-flush,Usable up to SIL 3 acc. to IEC 61508
Switching function : Normally closed (NC) Output type : NAMUR with safety function Rated operating distance : 40 mm Installation : non-flush Assured operating distance : 0 ... 32.4 mm Reduction factor rAl : 0.4 Reduction factor rCu : 0.3 Reduction factor r304 : 0.85 Safety Integrity Level (SIL) : up to SIL3 acc. to IEC 61508 Danger! In safety-related applications the sensor must be operated with a qualified fail safe interface from Pepperl+Fuchs, such as KFD2-SH-EX1.
Consider the exida Functional Safety Assessment document which is available on www.pepperl-fuchs.com as an integral part of this product's documentation. Output type : 2-wire Nominal voltage : 8.2 V (Ri approx. 1 kΩ) Switching frequency : 0 ... 100 Hz Current consumption : Safety Integrity Level (SIL) : SIL 3 MTTFd : 7560 a Mission Time (TM) : 20 a Diagnostic Coverage (DC) : 0 % Standard conformity : IECEx approval : ATEX approval : EAC conformity : TR CU 012/2011 UL approval : cULus Listed, General Purpose CCC approval : NEPSI approval : KCC approval : Ambient temperature : -40 ... 100 °C (-40 ... 212 °F) Connection type : screw terminals Core cross section : up to 2.5 mm2 , stripped insulation length: 7 mm Connection (system side) : screw terminals , M20 x 1.5 cable gland , usable thread length 10 mm , screw-in depth max. 10 mm Housing material : PBT Sensing face : PBT Degree of protection : IP68 Use in the hazardous area : see instruction manuals