Comfort series

Switching function : Normally closed (NC)
Output type : NAMUR
Rated operating distance : 2 mm
Installation : flush
Assured operating distance : 0 ... 1.62 mm
Actual operating distance : 1.8 ... 2.2 mm typ.
Reduction factor rAl : 0.23
Reduction factor rCu : 0.21
Reduction factor r304 : 0.7
Output type : 2-wire
Nominal voltage : 8.2 V (Ri approx. 1 kΩ)
Switching frequency : 0 ... 1000 Hz
Hysteresis : 1 ... 10 typ. 3 %
Reverse polarity protection : reverse polarity protected
Short-circuit protection : yes
Suitable for 2:1 technology : yes , Reverse polarity protection diode not required
Current consumption :
Switching state indicator : all direction LED, yellow
MTTFd : 2099 a
Mission Time (TM) : 20 a
Diagnostic Coverage (DC) : 0 %
Standard conformity :
IECEx approval :
ATEX approval :
EAC conformity : TR CU 012/2011
UL approval :
CCC approval :
NEPSI approval :
ANZEx : 18.3018X
KCC approval :
Ambient temperature : -25 ... 100 °C (-13 ... 212 °F)
Storage temperature : -40 ... 100 °C (-40 ... 212 °F)
Connection type : cable
Housing material : Stainless steel 1.4305 / AISI 303
Sensing face : PBT
Degree of protection : IP66 / IP67
Cable :
Scope of delivery : 2 self locking nuts in scope of delivery
Use in the hazardous area : see instruction manuals

  • 最小起订量 : 1